Zhejiang Jiangshan Hengli Electrical Co., Ltd. is one of the leading manufacturers and suppliers of 100kva energy efficient distribution transformers in China. If you're going to wholesale durable 100kva energy efficient distribution transformers made in China, welcome to get pricelist from our factory. All customized products are with high quality and low price.
The 100kVA Three Phase Energy Efficient Oil Immersed Distribution Transformer is designed to provide reliable power distribution with lower energy losses and improved long-term operating efficiency.
With a rated capacity of 100kVA, this transformer steps down 10kV medium voltage to 0.4kV low voltage, supplying stable three-phase power to commercial buildings, industrial facilities and public infrastructure.
Designed around Grade 2 energy efficiency requirements under China's GB 20052-2024 standard, this model delivers verified low-loss performance, with a factory test result of just 132W no-load loss and 1,260W load loss.
Compared with Grade 3 conventional transformer maximum allowable loss limits under the same standard, it achieves approximately 12% lower no-load loss and 20.3% lower load loss.
Featuring a grain-oriented silicon steel (CRGO) core, optimized winding design and ONAN cooling system, this transformer helps reduce energy consumption while maintaining reliable operation.
Manufactured by Zhejiang Hengli Electrical, it is suitable for distribution projects where energy efficiency, operating reliability and long-term cost control are important.
Technical Specifications
| Parameter | Specification |
| Product Type | Oil Immersed Distribution Transformer |
| Model Series | S20 |
| Rated Capacity | 100kVA |
| Phase | Three Phase |
| Primary Voltage | 10kV |
| Secondary Voltage | 0.4kV |
| Frequency | 50Hz |
| Vector Group | Dyn11 |
| Cooling Method | ONAN |
| Core Material | Grain-Oriented Silicon Steel (CRGO) |
| Winding Material | Copper |
| No-Load Loss | 132W |
| Load Loss | 1,260W |
| Tap Changer | Off-circuit Tap Changer |
| Tapping Range | ±2 × 2.5% |
| Rated Impedance | 3.9% |
| Insulation Medium | Mineral Transformer Oil |
| Energy Efficiency | Grade 2 |
| Applicable Standard | GB 20052-2024 or IEC 60076 and othet Applicable Standards |
Standards: IEC, GB, or customized requirements




Energy Efficiency and Actual Loss Performance
This 100kVA energy efficient distribution transformer is designed to meet Grade 2 energy efficiency requirements under China's national standard GB 20052-2024.
Grade 2 represents an energy-efficient level under the Chinese national classification. Compared with conventional transformer, it requires lower allowable no-load and load losses.
The actual factory test results of this transformer are:
No-Load Loss: 132W
Load Loss: 1,260W
Both values are below the corresponding Grade 2 maximum allowable limits, demonstrating its low-loss performance.
Actual Loss Performance Comparison
The following table compares the actual test results of this Hengli transformer with the Grade 2 and Grade 3 conventional transformer loss limits specified in GB 20052-2024.
| Technical Parameter | Hengli Actual Result | Grade 2 Limit | Grade 3 Limit |
|---|---|---|---|
| No-Load Loss | 132W | ≤135W | ≤150W |
| Load Loss | 1,260W | ≤1,265W | ≤1,580W |
| Total Loss at Rated Load | 1,392W | ≤1,400W | ≤1,730W |
The total loss at rated load is the sum of no-load loss and load loss.

Key Energy-Saving Advantages
Compared with the Grade 3 conventional transformer maximum allowable loss limits under GB 20052-2024, this transformer achieves:
1. 12% Lower No-Load Loss
The actual no-load loss is 132W, compared with the Grade 3 limit of 150W. Lower core losses help reduce continuous electricity consumption whenever the transformer remains energized, including during periods of low demand.
2. 20.3% Lower Load Loss
The actual load loss is 1,260W, compared with the Grade 3 limit of 1,580W. Optimized winding design and conductor selection help reduce current-related losses during operation.
3. 19.5% Lower Total Loss at Rated Load
At rated load, the combined no-load and load losses are 1,392W, compared with the Grade 3 reference limit of 1,730W. This lower loss level helps reduce operating energy consumption and supports long-term cost savings.
These percentages compare the actual Hengli test results with the Grade 3 conventional transformer maximum allowable limits. They are not guaranteed savings against every conventional transformer or under every operating condition.
Energy-Efficient Design Features

1. Grain-Oriented Silicon Steel Core
The magnetic core uses grain-oriented silicon steel (CRGO) with favorable magnetic properties. Optimized core design, accurate cutting and careful lamination assembly help reduce hysteresis and eddy current losses.
This directly contributes to lower no-load loss, particularly for transformers that remain energized continuously.
2. Optimized Copper Windings
Copper windings provide good electrical conductivity and mechanical strength. Appropriate conductor sizing and winding arrangements help reduce winding resistance and load losses while maintaining stable electrical performance.
3. Efficient ONAN Cooling System
The ONAN cooling system uses natural oil circulation and natural air circulation to dissipate heat without requiring forced cooling equipment.
Effective heat dissipation helps maintain suitable operating temperatures and supports long-term transformer reliability.

Customization Options
We provide tailored solutions to meet your project requirements:
● Customized voltage ratio (HV/LV)
● Copper or aluminum windings
● Low-loss or eco-design options
● Off-load or on-load tap changer
● Anti-corrosion coatings for coastal environments
● Compact or lightweight design solutions

Why Choose Us
● Direct factory supply with competitive pricing
● Support for OEM & ODM projects
● Fast response and flexible production capability
● Strict quality control and international standards compliance
● Reliable export experience for global markets

International Reference: IEC Energy Efficiency Standard
●IEC TS 60076-20:2017 provides an international framework for evaluating transformer energy efficiency based on power losses and the Peak Efficiency Index (PEI).
●Although GB 20052-2024 Grade 2 has no direct IEC grade equivalent, its actual no-load and load loss values provide useful reference data for international buyers comparing transformer energy performance.
●The two standards use different assessment methods and should be evaluated independently.
Quality Control and Factory Testing
At Zhejiang Hengli Electrical, transformer quality is verified through manufacturing inspections and electrical testing before delivery.
Typical routine tests include:
Winding resistance measurement
Voltage ratio and vector group verification
Impedance voltage measurement
No-load loss and no-load current measurement
Load loss measurement
Applied voltage withstand test
Induced voltage withstand test
Insulation resistance measurement
Transformer oil inspection
Oil leakage inspection
Particular attention is given to no-load and load loss measurements to verify the energy performance of the finished transformer.
Factory test reports can be provided to buyers for technical evaluation, quality verification and project acceptance.



FAQ
Hot Tags: 100kva energy efficient distribution transformers, China 100kva energy efficient distribution transformers manufacturers, suppliers, factory, 11KV 0 433kv Small Distribution Transformer, 500kva Power Distribution Transformer, Distribution Transformer Used for Lighting and Industrial Loads, High Voltage Distribution Transformer, Oil Cooled Small Power Distribution Transformer, Output Distribution Transformer